China Wholesale Disconnector Manufacturers – Vacuum Load Switch Fuse Combined Apparatus – Greenpower
China Wholesale Disconnector Manufacturers – Vacuum Load Switch Fuse Combined Apparatus – Greenpower Detail:
Model and Meaning
Ambient Condition
Environment temp: Max. temp. +40℃; Min. temp. -15℃
Environment humidity: Relative humidity per day ≤ 95%; Relative humidity per month ≤ 90
Altitude of site where the Switch service in can reach 1000m
For special service condition, please contact manufacturer
Reference Standard
GB3804-2004 High-Voltage alternating-current switches for rated voltage above 3.6kV and up to and including 40.5kV
GB16926-2009 High-Voltage alternating-current switch-fuse combinations
GB/T11022-1999 Common specifications for high-voltage switchgear and controlgear standards
Main Technical Parameters of Switch
Name |
Unit |
Switch GPL-24/T630-20 |
Switch-fuse Combination GPLR-24/T125-40 |
|
Rated voltage |
kV |
24 |
24 |
|
Rated frequency |
Hz |
50 |
50 |
|
Rated current |
A |
630 |
125 (as per fuse) |
|
Rated Insulation level |
1min power frequency withstand voltage |
kV |
Terminal contacts with breakers open 65; Phase to phase, phase to earth 65 |
|
Lightening impulse withstand voltage |
kV |
Phase to phase, phase to earth 125 ; Terminal contacts with isolators open 125 |
||
Rated short circuit breaking current |
kA |
- |
40 |
|
Active load breaking current |
A |
630 |
- |
|
Rated closing loop breaking current |
A |
630 |
- |
|
Active load low current breaking |
A |
31.5 |
- |
|
Rated cable charging breaking current |
A |
16 |
16 |
|
Rated short circuit making current (peak) |
kA |
50 |
100 |
|
Rated short time withstand current |
kA |
20 |
- |
|
Rated short time withstand current duration |
S |
4 |
- |
|
Rated peak withstand current |
kA |
50 |
- |
|
Rated take-over current |
A |
- |
3150 |
|
Circuit resistance |
μΩ |
≤150 |
≤250+ Fuse |
|
Motor power |
W |
90 |
||
Moving and fixed contact permissible abrasion accumulative thickness |
mm |
3 |
||
Clearance between open contacts |
mm |
12±1 |
||
Contact closing bouncing time |
ms |
≤2 |
||
3-phase asynchronous |
ms |
≤2 |
||
Average closing speed |
m/s |
0.8±0.2 |
||
Average opening speed |
m/s |
1.3±0.2 |
||
Mechanical endurance |
Times |
10000 |
Main Technical Parameters of Motor
Name |
Unit |
Parameters |
Rated operation voltage |
V |
AC/DC 110/220 |
Rated power input |
W |
80 |
Normal voltage range of charging motor |
|
85%~110% Rated operation voltage |
Charging time |
s |
≤15 |
Main Technical of Coil
Name |
Unit |
Parameters |
|
Rated operation voltage |
V |
AC, DC110 |
AC, DC220 |
Rated operation current |
A |
≤3 |
≤2 |
Normal voltage range of close coil |
|
85%~110% Rated operation voltage |
|
Normal voltage range of trip coil |
|
65%~120% Rated operation voltage |
Structure and Function
GPL(R) type switch consist of operating mechanism and arc-extinguish chambers in front-back arrangement, its main conductive circuit is of floor model structure. The vacuum arc-extinguish chamber is fixed in a vertical cannular insulation column structure made of epoxy resin by APG technology, therefore with very good anti-creepage Such structure design great that reduces the accumulation of dusts on the surface of vacuum arc-extinguish chamber, it not only can prevent the vacuum extinguish chamber from outside influence, but also can ensure to present high resistance state against the voltage effect even in warm-wet climate or heavy pollution environment.
The spring operating mechanism arranged in plane disposal can be charged by manual or motor, the operating mechanism located in the iron box fixed in front of arc-extinguish chamber. The box is divided into five assembly space by four clapboards, in this space there are charging section, diving section, releasing section and buffer of mechanism separately. The structure of GPL(R) type switch which the operating mechanism and arc-extinguish chambers are arranged into an integrate front-back layout can match well the operating performance of operating mechanism and the performance needed for breaking and making of arc-extinguish chamber. Also, can reduce the needless midway terms and reduce the noise and energy consumed therefore to lead the operation performance of GPL(R) much reliable.
Product detail pictures:
Related Product Guide:
We're going to commit ourselves to giving our esteemed customers along with the most enthusiastically considerate providers for China Wholesale Disconnector Manufacturers – Vacuum Load Switch Fuse Combined Apparatus – Greenpower, The product will supply to all over the world, such as: Kenya, Cyprus, Greece, During in 11 years, We have participated in more than 20 exhibitions, obtains the highest praise from each customer. Our company has been devoting that "customer first" and committed to helping customers expand their business, so that they become the Big Boss !
By Carol from Algeria - 2017.04.08 14:55
This is a very professional and honest Chinese supplier, from now on we fell in love with the Chinese manufacturing.
By Delia Pesina from Boston - 2017.10.25 15:53