China Wholesale Lbs Load Break Switch Suppliers – GPR-24(12)kV Series Ring Main Unit Switchgear – Greenpower
China Wholesale Lbs Load Break Switch Suppliers – GPR-24(12)kV Series Ring Main Unit Switchgear – Greenpower Detail:
Summary
GPR-24 series Ring Main Unit is an extensible, SF6 insulated switchgear, with rated voltage of 12&24 kV. All its HV live parts are contained in an air-tight gas tank, which is made from stainless steel of 3mm. The whole switching assembly is SF6 insulated, and free from any external influence, ensuring it great reliability of service and maintenance free. By plug-in type busbar extension, GPR-24 series Ring Main Unit can be of free combination and full modularization. The busbar extension has passed type test for power and thermal stability, and is fully insulated and shielded, exhibiting high reliability and safety. GPR-24 series Ring Main unit is suitable for all MV network up to 24 kV, all compact power stations, power distribution substations in all important industries, such as petrol-chemical industry, metallurgical and mining industries, and all transformer substations and wind power system.
Features
1. Advanced process technique for gas tank
The digital-controlled laser cutting and punching system and three-dimension and five-axis laser welding system imported from Germany with ensure the gas tightness and uniformity of all gas tanks.
The fully automatic and integral helium leak detection system, made by SEILER Vakuumtechnik GmbH, through detecting of Helium leakage by mass spectrograph, brings gas leakage rate per year down to less than 0.02%, ensuring the life span of gas tank of over 30 years.
Advanced process technique for parts .
All epoxy resin insulated parts, including insulated poles, are manufactured by fully-automatic and digitally controlled epoxy resin vacuum mixing/pressure gelatinizing system from Hedrich (Germany) .
The busbar connector, cable connector, end-plug and other silicone rubber insulated parts are manufactured by fully-automatic and digitally controlled silicone rubber mixing/pressure gelatinizing system from VOGEL(Switzerland).
2. Excellent solutions for products
With small and compact structure, the basic functional units K, T, V, B and C have uniform dimension: 350*800*1380 mm (width*depth*height) .
Complete solutions:
Single version: load break switch unit, switch-fuse unit, vacuum circuit breaker unit, busbar subsection unit, cable unit, metering unit, etc.
Block version can be made up of two, three, four, five or six functional units.
Single units and block version can be connected by busbar connectors flexibly.
3. Strong adaptability to the environment
The primary conductive system is fully sealed in the SF6 gas tank and will not be influenced by the outside environment, independent of the impact of dew, dust, salt fog, etc. Therefore, GPR-24 series can be applied at various severe service conditions.
12kV Technical Data
Description |
Unit |
LBS unit |
Switch-fuse unit |
VCB unit |
Busbar subsection unit |
|
Rated voltage |
kV |
12 |
12 |
12 |
12 |
|
Power frequency withstand voltage (1min) |
Phase to phase/earth |
kV |
42 |
42 |
42 |
42 |
Across the isolating distance |
kV |
48 |
48 |
48 |
48 |
|
Impulse withstand voltage |
Phase to phase/earth |
kV |
75, (95)* |
75, (95)* |
75, (95)* |
75, (95)* |
Across the isolating distance |
kV |
85, (110)* |
85, (110)* |
85, (110)* |
85, (110)* |
|
Rated frequency |
Hz |
50,60 |
50,60 |
50,60 |
50,60 |
|
Rated current |
A |
630 |
① |
630 |
630 |
|
Rated short circuit breaking current |
kA |
|
② |
20,(25)* |
|
|
Rated short time withstand current |
kA/s |
20/3, (20/4, 25/1)* |
|
20/3, (20/4, 25/3)* |
20/3, (20/4, 25/1)* |
|
Rated peak withstand current |
kA |
50, (63)* |
|
50, (63)* |
50, (63)* |
|
Rated short circuit making current |
kA |
50, (63)* |
② |
50, (63)* |
50, (63)* |
|
Rated transfer current |
A |
|
1800 |
|
|
|
Rated active load breaking current |
A |
630 |
|
|
630 |
|
Rated closed loop breaking current |
A |
630 |
|
|
630 |
|
5% rated active load breaking current |
A |
31.5 |
|
|
31.5 |
|
Rated operating sequence |
|
|
|
O-0.3s-CO-180s-CO |
|
|
Mechanical lifetime |
Ops. |
5000 |
5000 |
10000 |
5000 |
|
Electrical lifetime |
|
E3 |
|
E2 |
E3 |
|
Thickness of stainless steel |
mm |
3.0 |
||||
Rated SF6 pressure |
kPa |
30 (at 20℃, 101.3kPa) |
||||
Annual leakage rate |
<0.02% |
|||||
Water treatment test |
12kV 24 hours (at 30 kPa under the water) |
|||||
Internal arc test |
20kA 1s |
|||||
Protection degree |
Gas tank |
IP 67 |
||||
Fuse holder |
IP 67 |
|||||
GPR enclosure |
|
IP 4X |
24kV Technical Data
Description |
Unit |
LBS unit |
Switch-fuse unit |
VCB unit |
Busbar subsection unit |
|
Rated voltage |
kV |
24 |
24 |
24 |
24 |
|
Power frequency withstand voltage (1min) |
Phase to phase/earth |
kV |
50, (65)* |
50, (65)* |
50, (65)* |
50, (65)* |
Across the isolating distance |
kV |
64, (79)* |
64, (79)* |
64, (79)* |
64, (79)* |
|
Impulse withstand voltage |
Phase to phase/earth |
kV |
95, (125)* |
95, (125)* |
95, (125)* |
95, (125)* |
Across the isolating distance |
kV |
110, (145)* |
110, (145)* |
110, (145)* |
110, (145)* |
|
Rated frequency |
Hz |
50, 60 |
50, 60 |
50, 60 |
50, 60 |
|
Rated current |
A |
630 |
① |
630 |
630 |
|
Rated short circuit breaking current |
kA |
|
② |
20 |
|
|
Rated short time withstand current |
kA/s |
20/3, (20/4)* |
|
20/3, (20/4)* |
20/3, (20/4)* |
|
Rated peak withstand current |
kA |
50 |
|
50 |
50 |
|
Rated short circuit making current |
kA |
50 |
② |
50 |
50 |
|
Rated transfer current |
A |
|
1400 |
|
|
|
Rated active load breaking current |
A |
630 |
|
|
630 |
|
Rated closed loop breaking current |
A |
630 |
|
|
630 |
|
5% rated active load breaking current |
A |
31.5 |
|
|
31.5 |
|
Rated operating sequence |
|
|
|
O-0.3s-CO-180s-CO |
|
|
Mechanical lifetime |
Ops. |
5000 |
5000 |
10000 |
5000 |
|
Electrical lifetime |
|
E3 |
|
E2 |
E3 |
|
Thickness of stainless steel |
mm |
3.0 |
||||
Rated SF6 pressure |
kPa |
30 (at 20℃, 101.3kPa) |
||||
Annual leakage rate |
<0.02% |
|||||
Water treatment test |
24kV 24 hours (at 30 kPa under water) |
|||||
Internal arc test |
20kA 1s |
|||||
Protection degree |
Gas tank |
IP 67 |
||||
Fuse holder |
IP 67 |
|||||
GPR enclosure |
IP 4X |
Notes:
① Rated current of switch-fuse unit depends on the rating of fuse: ≤100A
② Rated short circuit breaking/making current of switch-fuse unit depends on the rating of fuse
* Values in brackets are for special requirements, please contact manufacturer or supplier for more information
GPR24 Series Overview
1. Single tank type
Note:
1. Values in brackets marked with”*” are the products at 24kV, power frequency withstand voltage of 65/79kV;
2. If there are too many secondary components in the configuration, an additional compartment for them can be installed on top of the panel, its height is 400mm.
2. GPR24 Block type-1 for 12kV &24kV(power frequency withstand voltage: 50/64kV)
Notes:
If there are too many secondary components in the configuration, an additional compartment for them can be installed on top of the GPR, its height is 400mm
Product detail pictures:
Related Product Guide:
We depend on sturdy technical force and continually create sophisticated technologies to meet the demand of China Wholesale Lbs Load Break Switch Suppliers – GPR-24(12)kV Series Ring Main Unit Switchgear – Greenpower, The product will supply to all over the world, such as: belarus, Lyon, Bahamas, We are trying our best to make more customers happy and satisfied. we sincerely hope to establish a good long-term business relationship with your esteemed company thought this opportunity,based on equal, mutual beneficial and win win business from now till the future.
By Elma from Angola - 2017.11.01 17:04
The company leader recept us warmly, through a meticulous and thorough discussion, we signed a purchase order. Hope to cooperate smoothly
By Matthew Tobias from Kenya - 2017.09.09 10:18