China Wholesale Load Break Switch Factory – 40.5kV Outdoor Vacuum Circuit Breaker – Greenpower
China Wholesale Load Break Switch Factory – 40.5kV Outdoor Vacuum Circuit Breaker – Greenpower Detail:
Model and Meaning
Use Environmental Conditions
a. Altitude: no more than 1000m
b. Ambient temperature: -15℃~+40℃, the daily average temperature does not exceed +35℃
c. Environmental humidity: daily average relative humidity: ≤95% monthly average relative humidity: ≤90%
Daily average vapor pressure: ≤2.2×10-3 MPa Monthly average vapor pressure: ≤1.8×10-3MPa
d. Earthquake intensity: no more than 8 degrees
e. Location of use: Ambient air is not appreciably polluted by dust, smoke, corrosive and/or flammable gases, vapors or salt mist.
Note: When the actual use environment does not meet the above conditions, please consult with our company.
Technical Parameter
No. |
Items |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
40.5 |
|||
2 |
Rated frequency |
Hz |
50 |
|||
3 |
1min power frequency withstand voltage |
Between poles, To earth |
kV |
95 |
||
Fractures |
118 |
|||||
Lightning impulse withstand voltage |
Between poles, To earth |
185 |
||||
Fractures |
215 |
|||||
4 |
Rated current |
A |
1250 1600 2000 2500 |
|||
5 |
Rated short-time withstand current (RMS) |
kA |
25 |
31.5 |
||
6 |
Rated peak withstand current |
63 |
80 |
|||
7 |
Rated short-circuit breaking current (RMS) |
25 |
31.5 |
|||
8 |
Rated short-circuit making current (peak value) |
63 |
80 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated sequence of operations |
O-0.3s-CO-180s-CO |
||||
11 |
Rated out-of-phase earth fault breaking current |
kA |
21.7 |
27.4 |
||
12 |
Rated cable charging current switching test |
A |
50 |
|||
13 |
Rated single/back-to-back capacitor bank breaking current |
800/800 |
||||
14 |
Mechanical life |
times |
10000 |
|||
15 |
Short circuit current breaking times |
times |
30 |
|||
16 |
Secondary circuit 1 min power frequency withstand voltage |
2000 |
||||
17 |
Rated operating voltage |
Closing coil |
V |
DC110/220, AC220 |
||
Opening coil |
V |
DC110/220, AC220 |
||||
18 |
Rated voltage of energy storage motor |
W |
DC110/220, AC220 |
|||
19 |
Rated power of energy storage motor |
s |
250 |
|||
20 |
Energy storage time (rated voltage) |
s |
≤10 |
|||
21 |
Rated pressure of SF6 gas (gauge pressure at 20°C) |
Mpa |
0.350+0.02 |
|||
22 |
Alarm pressure |
Mpa |
0.29±0.01 |
|||
23 |
Minimum functional pressure (blocking pressure) |
Mpa |
0.28±0.01 |
|||
24 |
Annual leak rate |
% |
≤0.5 |
|||
25 |
Gas moisture content |
μL/L |
≤150 |
|||
26 |
Moving contact stroke |
mm |
≥78 |
|||
27 |
Contact Spacing |
mm |
50±1.5 |
|||
28 |
Opening time |
ms |
60~78 |
|||
29 |
Closing time |
ms |
65~95 |
|||
30 |
Three-phase closing and opening are not periodic |
≤5 |
||||
31 |
Average opening speed (within 10ms after halfway) |
ms |
2.2~2.8 |
|||
32 |
Average closing speed (within 10ms after half-way) |
ms |
≥1.5 |
|||
33 |
Main conductive loop resistance |
μΩ |
≤32(Handcart) |
≤20(Fixed type) |
Main Structure
Product detail pictures:
Related Product Guide:
Reliable good quality and very good credit standing are our principles, which will help us at a top-ranking position. Adhering to your tenet of "quality 1st, purchaser supreme" for China Wholesale Load Break Switch Factory – 40.5kV Outdoor Vacuum Circuit Breaker – Greenpower, The product will supply to all over the world, such as: Curacao, French, Netherlands, Our products are exported worldwide. Our customers are always satisfied with our reliable quality, customer-oriented services and competitive prices. Our mission is "to continue to earn your loyalty by dedicating our efforts to the constant improvement of our items and services in order to ensure the satisfaction of our end-users, customers, employees, suppliers and the worldwide communities in which we cooperate".
By Eudora from Botswana - 2017.07.07 13:00
High Quality, High Efficiency, Creative and Integrity, worth having long-term cooperation! Looking forward to the future cooperation!
By Jerry from UK - 2018.02.21 12:14