China Wholesale Sf6 Vacuum Circuit Breaker Factory – 12 17.5 24kV Indoor Vacuum Circuit Breakers, GPVN-E Series – Greenpower
China Wholesale Sf6 Vacuum Circuit Breaker Factory – 12 17.5 24kV Indoor Vacuum Circuit Breakers, GPVN-E Series – Greenpower Detail:
Ambient Condition
Ambient temperature: -25℃~+45℃, daily average: ≤35℃
Altitude: 1000m(Standard); can up to 4500m for special ordering;
Relative humidity: daily average ≤95%, monthly average ≤90%;
Earthquake intensity ≤8 degree;
Applicable occasions should be free from inflammables, explosives, corrosives and severe vibration.
Model
GPVN -12Kv/17.5kV Indoor AC High Voltage Vacuum Circuit Breaker
Technical Specifications
No. |
Item |
Unit |
Data |
||||||
1 |
Rated voltage |
kV |
7.2~12(15/17.5) |
||||||
2 |
Rated frequency |
Hz |
50/60 |
||||||
3 |
Rated current |
A |
630,1000,1250 |
1600 |
2000,2500,3150 |
4000 |
|||
4 |
Rated short-circuit breaking current |
kA |
20 |
25 |
31.5 |
31.5 |
40 |
40 |
50 |
5 |
Rated short-circuit making current |
kA |
50 |
63 |
80 |
80 |
100 |
100 |
125 |
6 |
Rated short-time withstand current |
kA |
20 |
25 |
31.5 |
31.5 |
40 |
40 |
50 |
7 |
Rated peak withstand current |
kA |
50 |
63 |
80 |
80 |
100 |
100 |
125 |
8 |
Rated pull-out breaking current |
kA |
12.6 |
12.6 |
16 |
16 |
20 |
||
9 |
Rated out-of-phase earthing fault breaking current |
kA |
17.4 |
21.7 |
27.4 |
27.4 |
34.7 |
34.7 |
43.5 |
10 |
Rated short-circuit breaking current breaking time |
Times |
50 |
30 |
30 |
12 |
|||
11 |
Rated operation sequence |
O-0.3s-CO-180s-CO |
O-180s-CO-180s-CO |
||||||
12 |
Rated breaking current of single capacitor bank |
A |
630 |
||||||
13 |
Rated breaking current of back to back capacitor bank |
A |
400 |
||||||
14 |
1min. Power frequency withstand voltage |
kV |
Phase to phase/ to earth: 42, across open contacts:48 |
||||||
15 |
Lightning impulse withstand voltage |
kV |
Phase to phase/ to earth: 75, across open contacts:85 |
||||||
16 |
Mechanical life |
Times |
20000 |
||||||
17 |
Closing time |
ms |
≤75 |
||||||
18 |
Opening time |
ms |
≤60 |
||||||
19 |
Power storage time under rated voltage |
s |
≤10 |
Outline Dimension of GPVN-12E
GPVN-24□ Indoor AC High Voltage Vacuum Circuit Breaker
Technical Specification
No. |
Item |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
24 |
|||
2 |
Rated frequency |
Hz |
50/60 |
|||
3 |
Rated current |
A |
630 1250 1600 2000 2500 3150 4000 |
|||
4 |
Rated short-circuit breaking current |
kA |
20 |
25 |
31.5 |
31.5 |
5 |
Rated short-circuit making current |
kA |
50 |
63 |
80 |
80 |
6 |
Rated short-circuit withstand current(4s) |
kA |
20 |
25 |
31.5 |
31.5 |
7 |
Rated peak withstand current |
kA |
50 |
63 |
80 |
80 |
8 |
Rated out-of-step breaking current |
kA |
|
|
12.6 |
12.6 |
9 |
Rated breaking current of out-of-phase earth fault |
kA |
17.4 |
21.7 |
27.4 |
27.4 |
10 |
Rated breaking times of short-circuit breaking current |
Times |
50 |
|||
11 |
Rated operating sequence |
|
O-0.3s-CO-180s-CO |
|||
12 |
Rated breaking current of single capacitor bank |
A |
630 |
|||
13 |
Rated breaking current of back-to-back capacitor bank |
A |
400 |
|||
14 |
1min. Power frequency withstand voltage |
kV |
50 |
|||
15 |
Lightning impulse withstand voltage |
kV |
125 |
|||
16 |
Mechanical life |
Times |
20000 |
|||
17 |
Closing time |
ms |
75 |
|||
18 |
Opening time |
ms |
60 |
|||
19 |
Storage time under rated voltage |
s |
10 |
Dimension of GPVN-24E/(630~1250A) Breakers
Dimension of GPVN-24E/(1600~3150A) Breakers
Product detail pictures:
Related Product Guide:
We rely upon strategic thinking, constant modernisation in all segments, technological advances and of course upon our employees that directly participate inside our success for China Wholesale Sf6 Vacuum Circuit Breaker Factory – 12 17.5 24kV Indoor Vacuum Circuit Breakers, GPVN-E Series – Greenpower, The product will supply to all over the world, such as: Jamaica, moldova, Tajikistan, We focus on providing service for our clients as a key element in strengthening our long-term relationships. Our continual availability of high grade products in combination with our excellent pre-sale and after-sales service ensures strong competitiveness in an increasingly globalized market. We are willing to cooperate with business friends from at home and abroad and create a great future together.