Ambient condition
Ambient temperature: -25℃~+45℃, daily average: ≤35℃
Altitude: 1000m( Standard); can up to 4500m for special ordering;
Relative humidity: daily average ≤95%, monthly average ≤90%;
Earthquake intensity ≤8 degree;
Applicable occasions should be free from inflammables, explosives, corrosives and severe vibration.
Model
Products feature
1) This product is applicable for our own made GPVN-12kV/17Kv/24kV embedded or insulating sleeve vacuum circuit breaker or ABB’s VD4 vacuum circuit breaker.
2) Our production configuration GPVC vacuum contactor – fuse combination or ABB company’s VC vacuum contactors, which can be composed of F-C loop cubicle, to meet the electricity system of power plants and demand of other industrial and mining enterprises.
3) Using excellent aluminum-zinc clad steel plate by precision CNC machining equipment assembled into the cabinet, and the use of double bending process, greatly improve the strength of the cabinet.
4) Door surface by epoxy resin electrostatic powder spray process, resistance of corrosion, oxidation, impact and strong adhesion.
5) Cabinet fully enclosed structure is realized fully armored, the functional units are completely separated. When the door is closed, it can achieve the operation of circuit breaker and earthing switch.
6) Precision screw drive mechanism, ensure the trolley with good interchangeability.
7) Perfect primary plan to meet the various needs of users, and enables double trolley plan.
8) Fast grounding switch for earthing and short circuits, and to achieve electric (Motorized) operation.
9) Simple and effective “Five Safety” interlock mechanism can reliably prevent misuse and ensure operator’s safety.
10) Switchgear is belonging to Arc-proof type, on the top of bus compartment, Vacuum circuit breaker compartment, and cable terminal compartment are equipped with pressure relief devices.
11) Cable compartment has ample space, can be easily connected to a plurality of cables, and make sure the installation height of the cable plug.
12) Strict protection rating (IP4X), to effectively prevent foreign matter or pest invasion.
13) Optional secondary system following the security monitoring device has a self-diagnostic function and data communication, intelligent integrated computer, to achieve remote control, remote telemetry, remote viewing, remote adjustment.
14) Meet GB3906, GB / T11022, DL404 and IEC60298, IEC62271-1 standards, and through a comprehensive test type test and plateau test (3000 m).
15) Passed electromagnetic compatibility tests in the high voltage equipment test laboratory.
A.Technical specification For 12Kv switchgear
Item |
Unit |
Data |
|
Rated voltage |
kV |
6~12 |
|
Rated frequency |
Hz |
50/60 |
|
Rated current |
A |
630~4000 |
|
Rated insulation level |
1min power frequency (Phase to earth / across open contacts) |
kV |
42/48 |
Lightning impulse withstand voltage (Phase to earth/across open contacts) |
kV |
75/85 |
|
Main busbar rated current |
A |
1250,1600,2000,2500,4000 |
|
Sub-busbar rated current |
A |
630,1250,1600,2000,2500,3150 |
|
Rated short time withstand current(4s) |
kA |
16,20,25,31.5,40,50 |
|
Rated peak withstand current |
kA |
40,50,63,80,100,125 |
|
Protection degree |
Enclosure IP4X, IP2X(VCB door opened) |
||
Outline dimension(width/depth/height) |
mm |
650(800,1000) /1500(1300,1670,2000) /2300 |
|
Weight |
kg |
500~1200 |
Structure drawing of cubicle 630A~1250A
Structure drawing of cubicle 1600A~4000A
B.Main technical parameters table for 17.5kV switchgear
No. |
Name |
Unit |
Data |
|
1 |
Rated voltage |
kV |
15/17.5 |
|
2 |
Rated insulation level |
1 min power frequency withstand voltage (RMS) |
kV |
50 |
Lighting impulse withstand voltage (peak) |
95 |
|||
3 |
Rated current |
A |
630~4000 |
|
4 |
Rated short-circuit opening current |
kA |
50 |
|
5 |
Rated power frequency |
Hz |
50/60 |
|
6 |
Rated short-circuit making current(peak) |
kA |
130 |
|
7 |
Rated peak withstand current |
kA |
130 |
|
8 |
Rated short-time withstand current |
kA |
50 |
|
9 |
Electrical life |
times |
20 |
|
10 |
Rated short-circuit current duration |
s |
4 |
|
11 |
Mechanical life of VCB |
times |
10000 |
|
12 |
Protection degree of cubicle |
Enclosure IP4X, IP2X(VCB door opened) |
||
13 |
Outline dimension (W*D*H) |
mm |
800/1000*1500/1670*2300 |
|
14 |
Weight |
kg |
500~1200 |
C.Technical specification for 24kV switchgear
Item |
Unit |
Data |
|
Rated voltage |
kV |
24 |
|
Rated frequency |
Hz |
50/ 60 |
|
Rated current |
A |
630,1250, 1600, 2500, 3150, 4000 |
|
Rated insulation level |
1min power frequency (phase to earth / across open contacts) |
kV |
65 |
Lightning impulse withstand voltage (phase to earth / across open contacts) |
kV |
125 |
|
Rated short time withstand current(4s) |
kA |
20, 25, 31.5 |
|
Rated peak withstand current |
kA |
50, 63, 80 |
|
Protection degree |
Enclosure: IP4X, door open: IP2X |
||
Outline dimension(width x depth x height) |
mm |
1000(800)x1820(1500)x2430(2300) |
|
Weight |
kg |
1200-1500 |
1. The short circuit capacity of CT shall be separately considered;
2. The diagram of back overhead outgoing line should have additional cubicle.
Structure schematic drawing of GPN1-24kV section drawing of feeder panel
Product detail pictures:
Related Product Guide:
We are commitment to offer the competitive price ,outstanding products quality, as well as fast delivery for China Wholesale Thermal Circuit Breaker Factory – GPN1-12kV Removable AC Metal-clad Enclosed Switchgear – Greenpower, The product will supply to all over the world, such as: Paraguay, Juventus, Senegal, Selling our products and solutions causes no risks and brings high returns to your company instead. It is our consistent pursuit to create value for clients. Our company is looking for agents sincerely. What are you waiting for? Come and join us. Now or never.
By Jerry from Sri Lanka - 2018.09.19 18:37
The quality of the products is very good, especially in the details, can be seen that the company work actively to satisfy customer's interest, a nice supplier.
By Hellyngton Sato from Marseille - 2018.06.09 12:42