Ambient Condition
Altitude: 1000m(Standard); can up to 4500m for special ordering;
Ambient temperature: -25℃ ~+45℃;
Relative humidity: daily average ≤95%, monthly average ≤90%;
Earthquake intensity: ≤8 degree;
Applicable occasions should free from inflammables, explosives, corrosives and severe vibration.
Model
Structure Feature
1. The arc-extinguish chamber is on the upper part and the mechanism is on the lower part. This structure is convenient for debug.
2. Complex insulating structure using air and organic material; Compact dimension and small weight.
3. Vacuum arc-extinguish chamber of Cutler-Hammer Company (USA) and domestic ZMD are both applicable for the VCB. Both two kinds of chambers extinguish arc by vertical magnetic field and featuring with low cut-off and good on-off capability with asymmetry.
4. Simple spring operation mechanism is free from maintenance within 10000 times of operations.
5. Lead-screw propeller, easy and stable operation and good self-locking capability.
Technical Specification
No. |
Item |
Unit |
Data |
1 |
Rated voltage |
kV |
36/38/40.5 |
2 |
1min. Power frequency withstand voltage |
kV |
95 (118, isolating distance) |
3 |
Lightning impulse withstand voltage(peak) |
kV |
185 (215 isolating distance) |
4 |
Rated current |
A |
630,1250,1600,2000, 2500 |
5 |
Rated short-circuit breaking current |
kA |
20, 25, 31.5 |
6 |
Rated short-circuit making current(peak) |
kA |
50, 63, 80 |
7 |
4s rated short-time withstand current |
kA |
20, 25, 31.5 |
8 |
Rated peak withstand current |
kA |
50, 63, 80 |
9 |
Rated operation sequence |
O-0.3s-CO -180s-CO |
|
10 |
Breaking times of rated short circuit breaking current |
Times |
30 |
11 |
Mechanical life |
Times |
10000; 20000 (for magnet type) |
12 |
Rated frequency |
Hz |
50/60 |
13 |
Rated breaking current of capacitor bank |
A |
400 |
Technical Specification Of Storage Motor Of Operating Mechanism
No. |
Rated voltage |
Rated output power |
Normal operate voltage |
|
HDZ-22301B |
DC110V AC110V |
DC220V AC220V |
≤230W |
85%-110% rated voltage |
Outline And Dimension Of Installation
Secondary Diagram
Product detail pictures:
Related Product Guide:
So that you can finest fulfill client's demands, all of our operations are strictly performed in line with our motto "High Excellent, Competitive Price, Fast Service" for China Wholesale 11Kv Vacuum Circuit Breaker Factory – GPVN-40.5kV Indoor AC High Voltage Vacuum Circuit Breaker – Greenpower, The product will supply to all over the world, such as: Bahrain, Lisbon, Bhutan, We have advanced production technology, and pursuit innovative in goods. At the same time, the good service has enhanced the good reputation. We believe that as long as you understand our product, you need to be willing to become partners with us. Looking forward to your inquiry.