• sns021
  • sns041
  • sns031

12kV/24kV PT Trolley

Short Description:

Application

The 24kV withdrawable transformer trolley has the characteristics of perfect design, compact structure, easy operation and excellent performance. It is suitable for high-voltage middle cabinets, where PT can be quickly drawn out and moved in to reduce the power failure switching time. The high-voltage fuse uses a miniature fuse with a diameter of 25mm and a length of 355mm, which is directly installed in the insulating contact arm. There are two sizes of PT vehicles, which are used in 800-wide cabinets and 1000-wide high-voltage center cabinets.


Product Detail

Product Tags

Technical Parameters

No.

Item

Unit

Data

1

Rated voltage (Ur)

V

12/24

2

High voltage fuse current (lr)

A

3.15A

3

Transformer rated capacity

kVA

3~5

4

Rated short-time withstand voltage (Ud)

kV

50

5

Rated lightning impulse withstand voltage (Up)

kV

125

6

Mechanical life

Class

M1/M2

7

Isolation handcart status and position indication communication module Modous (RS485)

-

Optional

8

Electric operation module

-

Optional

Dimensions of 12kV

Rated current

P

A

B

C

D

E

630A

150

502

532

490

202

100

210

652

682

638

277

160

275

852

882

838

377

200

8

Dimensions of 24kV (For 1000width cabinet)

9

Dimensions of 24kV (For 800width cabinet)

10

12Kv / 24kV Isolating Trolley(Busbar Trolley, Disconnecting Trolley)

Application
The 24kV withdrawable isolated trolley has the characteristics of perfect design, compact structure, easy operation and excellent performance. The product conforms to IEC62271-102 “High-voltage switchgear and control equipment-Part 102 AC disconnectors and grounding switches”. Suitable for high-voltage central cabinets, suitable for air-insulated indoor withdrawable central switch cabinets, for the main circuit to be switched under no-load conditions, and the circuit breaker being repaired waiting for electrical isolation of electrical equipment from live lines It has a safe interlocking device with the door.

Technical Parameters

No.

Item

Unit

Data

1

Rated voltage (Ur)

V

12/24

2

Rated current (lr)

A

630/1250

3

Rated short-time withstand current (lk)

kA

25

4

Rated short-circuit duration (tk)

s

3

5

Rated short-circuit peak current (lp)

kA

65

6

Rated short-time withstand voltage (Ud)

kV

50

7

Rated lightning impulse withstand voltage (Up)

kV

125

8

Mechanical life

Class

M1/M2

9

Isolation handcart status and position indication communication module Modous (RS485)

-

Optional

10

Electric operation module

-

Optional

Dimensions of 12kV

11

  • Previous:
  • Next:

  • Related Products

    
    >